Skip to playerSkip to main content
  • 2 days ago
In this session you will understand
1. Scenarios of Overpressure & how to calculate relief load for that
2. Relief load for Control valve Failure case
3. Relief load for blocked outlet
4. Reflux failure
5. Tube rupture
6. Cooling water failure
7. Fin fan cooler failure
Transcript
00:01hi friends welcome to the channel we are in module 1 for pressure relief fall and
00:06this is a session 3 on relief load for non-fire contingencies and this is a part 1 before that
00:13we have completed the relief load calculation for fire case so let's start disclaimer for
00:21our channel and the content you shown in this videos over pressure scenario in process industry
00:29these are listed here and which we are seen in detail in earlier session and we have covered
00:35the relief load calculation for external fire case and now we will see for the other cases
00:42control wall failure
00:47control wall generally installed with a fail open fail close or fail safe position
00:53but when we are calculating the relief load irrespective or regardless of its position
00:59safe position it has to be considered for a failure like if it is a fail say a fail closed
01:05then it has
01:06to be considered as fail open for the calculating the relief load
01:11also when we are calculating the relief load we have to consider the installed cv
01:17or the coefficient of discharge for the control wall
01:22and the maximum flow through the installed cv the installed cv generally given by the vendor and
01:29the on the given installed cv we have to calculate the maximum flow for the relief load
01:38so when we are calculating the relief flow on cv we have to consider we have to calculate it on
01:46minimum pressure or the permanent pressure drop not on the normal pressure drop it should be the
01:51minimum pressure drop so this is a general schematic of control wall some control walls will have a bypass
02:00so once we it have a bypass it has requirement to calculate the relief load calculation in case of
02:07failure of control wall as well bypass there is a different requirements
02:12so when control wall is having bypass the cv for the bypass wall all should not in should not be
02:22higher
02:22than the cv of the control wall and it shall it can be considered as the same cv of the
02:28control wall
02:34so in some cases uh it has considered that the control wall will fail open as well as the bypass
02:41wall will
02:42partially open so in that case we have to consider the total flow through the control wall
02:48on the installed cv with the minimum pressure drop as well as 50 percent of the bypass wall cv which
02:59is
02:59generally equal to the 50 percent of your installed cv of the main control wall
03:06that is regardless of actual size of bypass wall and if the bypass wall considered to be wide open
03:13with the control wall closed or blocked in then relieving rate in that case has to be calculated
03:19on the wide open bypass wall and we have to consider the bypass wall installed cv generally
03:26the normal wall or a manual wall having a higher cv than the control wall so this case has to
03:32be
03:33considered separately for the relief load calculation the manual wall should be considered
03:40are passing its capacity at full open position with the pressure in the vessel at relieving condition
03:46so whatever when we are calculating the relief load the relief load has to be calculated on the
03:51relieving condition not on the operating condition of the wall or not on the maximum pressure of the wall
03:56it should be on the relieving condition if control wall operates at 10 bar but however the set pressure
04:01of the psv is at 15 bar the relieving condition has to be calculated on the 15 bar
04:07so to calculate the flow rate through the control valve for the control valve failure case
04:13control valve will be used for either liquid or vapor or steam so to know the flow rate from the
04:20selected
04:21cv or the installed cv if we have a cv value then we can calculate through the formulas given in
04:28this
04:28slide so for the liquid flow rate the relief load will be 27.3 into installed cv or a selected
04:38cv given on
04:39the data sheet of existing wall into density of liquid into a square root of density of liquid into
04:49inlet pressure of the control valve and p2 is the relieving pressure of or the set pressure of the
04:58relief wall for the vapor flow rate if vapor is critical flow the critical flow defined as
05:07when p2 is less than or equal to 0.5 of p1 means if the in if the inlet pressure
05:16is 50 bar and outlet
05:17pressure is 20 or your psv set pressure is 10 bar or 20 or 15 bar which is less than
05:24half of the
05:26inlet pressure inlet pressure so in that case your flow vapor flow will be the critical so for critical
05:33flow to calculate the relief rate on the selected cv is 56.9 into installed or selected cv into p1
05:45square root of molecular weight by inlet temperature t1 and for non-critical vapor where the inlet pressure
05:56is or you can say outlet pressure is more than half of the inlet pressure if inlet pressure is 50
06:04bar
06:04and outlet pressure is 35 bar or a 30 bar then this is a non-critical vapor vapor flow so
06:11for that
06:12you can use the this to any two of the formula if you know the density you can go with
06:16the first
06:17formula if you know the molecular weight you can go with the second formula
06:21so in this formula w is the relieving capacity cv is the control valve coefficient which is the
06:30this is the selected one i am repeatedly telling not the normal or required cv it is the installed cv
06:40p1 is the pressure at control valve inlet based on the normal operating pressure p2 is the pressure of the
06:45control valve at outlet that is equal to the psp relieving pressure and unit also has to be
06:52considered it's all in absolute m is the molecular weight t1 is the temperature at control valve inlet
07:05so based on these formulas we can calculate the relief load for liquid in from the control valve as well
07:15as the vapor for critical and non-critical both the cases and if it is a steam then
07:23for stream for critical steam flow again the critical steam flow means your p2 is less than or equal to
07:320.5 of p1 which is same if it is a 50 bar inlet pressure and outlet was 15 or
07:39less than 25 then it
07:41is a critical flow so for that critical flow we have to use the formula for really flow w is
07:4611.76 into
07:48selected cv or installed cv into inlet pressure divided by 1 plus t into TCH and for non-critical flow
07:59rates
07:59we have to this TCH is the steam degree superheat which is the superheated temperature minus saturated
08:08temperature at that for the steam for that condition it is in Kelvin so for so for critical steam
08:17flow and non-critical steam flow we have to use this formula to calculate the relief flow from the
08:21control valve
08:25there is a one alternate method for calculation the cv which is when we we initially starting
08:33the psv calculation and we do not have the control valve information we only have the control valve
08:39calculated cv and we do not know what vendor is going to give us
08:44in such cases in such cases when we are working in the feed stage of the project or early design
08:49stage of the project
08:52so to calculate the process require so for that what we have to do we have to calculate the cv
08:57based on the process requirement suppose that calculated cv comes around 100
09:07then the selected cv to be considered as 200 percent of the calculated cv so you have to consider
09:15200 as a selected cv or a installed cv which is going to be installed on vendor which is
09:22which will be given by the vendor this is for the earlier calculation and if you have to consider
09:29the bypass for that control valve and your scenario is like control valve failure as as well as bypass
09:37valve is partially open in that case you have to consider 300 percent of the calculated cv so this
09:44is the calculated cv 100 is our calculated cv this is our installed cv
09:51so in case of bypass the cv will becomes 300 so when you calculate the flow rate considering the cv
10:02value
10:02of 300 in earlier formulas for liquid critical vapor non-critical vapor or steam or non-critical steam
10:10then you will get the relief load for the during the design stage
10:16uh design stage itself and that can be used to calculate the orifice size for the psv
10:25so in simple way 100 percent cv is the pressure required uh process required cv then 200 percent
10:32is the maximum cv value or you can say installed cv value and three percent c 300 percent cv is
10:38the
10:38maximum cv plus bypass valve open so in this way we can calculate uh relief load during the early design
10:45stage of the project or during the feed stage of the project the second scenario non-fire case is
10:53blocked outlet or a closed outlet so suppose in this schematic this is a column and column overhead
11:02having the vapor which is getting condensed in air fin fan cooler then uh water cooler and then it is
11:08getting separated separated in a separator reflux drum and vapors or lighters are going to further
11:15processing and then reflux is sent back to the column and overhead product is taken out parallelly
11:24so suppose this pressure control wall on the uh reflex drum get closed
11:33or this will be considered as a block outlet so it is blocking the vapor pass out of the reflux
11:40drum
11:40so what will happen it start increasing pressure in the reflux drum and that will govern your pressure
11:46of the column as well so that's why we have to install a pressure relief wall and we need to
11:53get the relief load for this pressure safety wall
12:01so the capacity of generally in the relief wall in a block outlet case is at least the capacity of
12:07the
12:07source pressure so whatever the my source pressure is the same capacity i have to use for the
12:13relief load calculation in block outlet the quantity of material to be relieved should be determined
12:20at the condition that correspond to the set pressure plus over pressure instead of normal operating condition
12:28so basically when it is a block outlet case liquid relief you have to consider the maximum liquid
12:33pumping rate and for vapor relief the total incoming stream vapor generated during the relieving condition
12:41and all the so in simple way from the block outlet case you have to consider the maximum inlet flow
12:49from
12:49that line or from that system or from that from that vessel to be considered however the relieving however
12:59the properties or the rate has to be calculated on set pressure plus over pressure instead of normal
13:08operating pressure that points has to be understood
13:12so third case is the cooling water or column reflux or a pump around failure
13:18so when reflux flow failures the failure cause the flooding of the condenser which is equivalent to
13:26the pressure relief wall capacity so when the reflux flow closed it will have a it will give the impact
13:34it will flood the condenser and the total capacity of your condenser is the your relief load for that scenario
13:42however it has to be noted that when the composition which is coming out of a condenser is different in
13:53normal
13:53operating case and when it is in a failure case of reflux your composition will be changed in the column
14:01itself
14:01because we do not have there may be some heaviest also traveling towards the vapor side because you do not
14:10have the reflux
14:10so compositional change has to be considered and to be taken care of case by case
14:17usually pressure relief size for the tower head with adequate conditions but each case must be examined
14:24what i said now if the pump around failure case basically what is the pump around in a column
14:32when there is a lot of heat in the field is available it will be cooled uh to like preheating
14:40for the preheating
14:41for the other uh feed or the product and the column uh it will be taken out of the column
14:49it will be cooled
14:50and again sent back on the top trays of the column so that will remove your uh that will reduce
14:56your load on
14:56the condenser and this will uh help in uh recovering the heat that's why pump around are given to the
15:05column
15:06however uh if the pump around duty is very high the functional high and highly superheated then pump if
15:16the loss of pump around will uh will increase your uh reduction in tower cooling and result in dry
15:24running of the tower so that case to be considered the potential dryout should be evaluated this tray
15:30will be completely get dry if your pump around stops and the relief load due to the fractionated
15:38dryout is usually the sum of your vapor entering to the column which is to the feed itself
15:44and plus if you are putting any stripping stream into this or you have a reboiler in this so whatever
15:51the duty of this reboiler or vapor generated through this reboiler or you have a stripping stream
15:58and the vapor available in your feed that the total will be your relief load so that's why in
16:07uh non-firing fire case scenarios we do not have much calculation but we need to engineering judgments
16:14to be taken the relief flow requirement in the vaporization rate caused by an uh amount of heat
16:22equal to the removed by the pump around so latent heat of vaporization will be corresponding to the latent
16:27heat under relieving conditions so uh when this vapors heat load we have to consider the latent heat
16:35uh for vaporization will be corresponds to the latent heat under relieving conditions so
16:40when we are calculating all the relieving cases it should be noted that all the relieving should be
16:46calculated on the relieving pressure only not on the operating conditions
16:52if it is a total condensing the relief load requirement is equal to the total incoming vapor
16:57rate of the condenser so whatever vapors coming from the condensers or the tower
17:02it will be your relieving rate and similarly you have to calculate the composition and the
17:13composition based on the relieving condition not on the operating condition
17:20and if the search capacity of overhead generally search capacity remains around 10 minutes
17:25in the enured condenser so your failure is more than 10 minutes it means you already lost complete
17:32reflux so whatever the vapor coming from the tower that will be your relieving load
17:39in partial condensing basically in partial condensing what happen uh vapor are not getting completely condensed
17:47so incoming is vapor and outgoing is two phase flow maybe partially liquid and partially vapor so in that case
17:56you have to take difference like uh 100 kgs or 100 kg per hour vapors are coming and 50 kg
18:04are getting
18:06condensed and 50 kg are still vapor so the load for the relief in this case has to be considered
18:12for the 50 kg per hour
18:14only but that also on the relieving conditions
18:23louver closer so louvers are installed on the thin fan coolers generally if the louvers get closed which
18:29are on the top of here if the louvers get closed you are not able to pass the air through
18:34the thin fan
18:35cooler so in that case it has to be considered as total failure of the coolant and whatever the load
18:42vapor load coming to this cooler has to be considered for the relieving capacity
18:48top reflux failure
18:52it is the uh the total incoming steam vapor plus generated within the relieving condition
18:58less the vapor condensing by the side stream refluxes
19:02so basically top reflux failure means
19:05it has to be again the total vapor coming which is getting condensed and
19:11whatever the only ref because of the reflux whatever the it means the condensers are working
19:17however the reflux pumps has stopped so whatever the cooling happen by the reflux that has to be minused
19:23from the and that to be considered for the relief load not the complete condenser load
19:32if the side stream reflux failure difference between the vapor entering and leaving to that
19:36section has to be considered if fan failure considered for this fan no louvers close nothing
19:43only the fan get tripped then we can have we can consider some uh partial condensation because of
19:50the natural convection and that that remains around 20 to 30 percent suppose the the load of this is
20:00100 kilojoule per kilo cal per hour so 20 to 30 percent of it so you can say 80 percent
20:07will uh suppose if it we consider the 20 percent margin so 80 percent 80 kilo cal per hour should
20:14be your relieving rate in that case due to we will get the margin of 20 percent based on the
20:20natural draft convection
20:24solution thank you very much and follow our channel like and subscribe it and if you have any comments
20:31uh we are we are happy to answer it you can write us your comment on conceptengineering2025gmail.com
20:40link for other sessions are also given in the description box so
20:43please go through the other lectures as well thank you
Comments

Recommended